CHIEF.
Web appLearnPlatformFeaturesFor employers
UTC --:--:--Open web app
Web appLearnPlatformFeaturesFor employersContact
Open web appiOS app on the App Store →
Learn/Star–Delta Connection/Guides
ENES

Starting methods on board: DOL, star–delta, soft starter, VFD

CHIEF. LEARN · Guide 5 of 6

Direct-on-line, star–delta, soft starter or frequency converter on a ship, and what a starter does after a blackout: low-voltage protection (LVP) or release (LVR).

The example throughout is the main fire pump of a platform supply vessel: a 37 kW cage motor on a 440 V, 60 Hz supply, full-load current 61 A, started star–delta from the main switchboard.

MC
main contactor
LVP
low-voltage protection
LVR
low-voltage release

Why not start everything direct-on-line

Why not start everything direct-on-line? The generator decides. A 37 kW start on a 625 kVA generator is manageable. A 200 kW ballast pump, or a big motor on the emergency generator, is not.

Star–delta is cheap and simple, which is why it is still common on fire, ballast and cooling water pumps and on fans.

Soft starter and frequency converter

A soft starter ramps the voltage up with thyristors. There is no changeover surge, but the torque is still reduced. A frequency converter starts at low frequency with full torque and the lowest current, at a higher price, with harmonics to deal with on the switchboard.

After a blackout: LVP and LVR

After a blackout. This starter has low-voltage protection (LVP): when the supply fails, MC drops out and its holding contact opens, so when the voltage comes back the pump stays stopped until someone presses START. A starter with low-voltage release (LVR) drops out too, but closes again by itself as soon as the voltage returns.

Rules differ on which a fire pump should have. US rules ask for LVR on fire pump controllers where an automatic restart is not hazardous (46 CFR 111.70-3). With an unattended engine room and one generator on the board, SOLAS asks for the standby generator to start and connect by itself, with automatic restart of essential auxiliaries, in sequence where necessary (II-1/53.2.1). Many ships keep LVP on the starters and let the power management system restart them one after another.

A star–delta starter that restarts goes through star again, because its timer reset when the supply was lost. That is exactly what the generator needs when many motors come back at once.

Try it in the simulator. Wire the starter, set the timer and the overload relay, then find the hidden faults in a fire drill on a 3D vessel. Free, in your browser, no account.

Open Star–Delta Connection →

Check yourself

The main generator trips while this fire pump runs. 25 s later the standby generator is on the MSB. What does the pump do?
  1. Stays stopped until someone presses START — correct
  2. Restarts by itself straight in delta
  3. Restarts by itself in star, then changes over

MC dropped out when the supply failed, and its holding contact 13–14 opened with it. Nothing closes MC again when the MSB comes back: that is low-voltage protection. Start it again from the bridge. A starter with low-voltage release would restart by itself, and it would go through star again, because the timer reset.

Sources

  • 46 CFR 111.70-3, motor controllers, incl. low-voltage release for fire pumps (eCFR)
  • SOLAS II-2/10, fire fighting: fire pumps, fire main, hydrants (consolidated text, imorules.com)

For training only. Models are simplified; class rules and IMO texts are the authority.

← PreviousOverload relay setting and direction of rotationNext →The fire main isolating valve and the emergency fire pump
Built by CHIEF.

Free for seafarers: CV, certificates, sea service

These trainers are made by CHIEF., the career platform for seafarers. Keep your STCW certificates with expiry reminders, log sea service and send a ready CV to crewing companies.

Free to startiPhone and any browserOne account
Create a free accountiOS app on the App Store →

Already have an account? The button opens it.

CHIEF.
LearnCertificate trackerCV builderSeafarer CVSTCW certificatesSea-time calculatorWeb appiOS appContact
© 2026 CHIEF. · Maritime Reconnected
support@chief.directPrivacyTermsUAru