The fire main isolating valve and the emergency fire pump
CHIEF. LEARN · Guide 6 of 6
Why the engine room part of the fire main has an isolating valve (SOLAS II-2/10), how the emergency fire pump and SDNR valves work together, and the test.
The example throughout is the main fire pump of a platform supply vessel: a 37 kW cage motor on a 440 V, 60 Hz supply, full-load current 61 A, started star–delta from the main switchboard.
- SDNR
- screw-down non-return valve
- PSV
- platform supply vessel
Why the isolating valve
A fire in the engine room can take out pump No.1, its supply and the fire main around it. So the engine room section of the main has an isolating valve outside the machinery space, where a man can still reach it in a fire. With that valve shut, every hydrant outside the engine room must still get water from another pump or the emergency fire pump (SOLAS II-2/10.2.1.4.1).
The emergency fire pump
On this PSV the emergency fire pump stands in the bow thruster room, with its own sea chest, and runs from the emergency switchboard. In a blackout the emergency switchboard is dead until the emergency generator takes it over, a few seconds later. The pump’s direct-on-line starter holds itself in, so it stops when the emergency switchboard goes dead and has to be started again from the bridge.
Each pump discharges through a screw-down non-return valve (SDNR). With pump No.1 stopped and the isolating valve open, water from the emergency pump reaches the engine room hydrant but cannot run back through pump No.1 to the sea. With pump No.1 running and two jets open, the main sits above the emergency pump’s shut-off head and its SDNR stays shut.
Capacity and pressure
Size (FSS Code, chapter 12): at least 40 % of the total capacity required of the fire pumps, and never less than 25 m³/h on a cargo ship of 2000 GT and over. IMO MSC.1/Circ.1314 reads the hydrant pressure it must hold as 0.27 N/mm². In the simulator’s model it gives 43 m³/h and 3.1 bar with two jets on the forecastle.
The emergency fire pump test
The emergency fire pump test proves the arrangement, not only the pump: isolating valve shut, emergency pump started from the bridge, two jets from the forecastle hydrants at the required pressure. Then the valve goes back open. Left shut, it keeps pump No.1 off the deck at the next fire.
Hoses and pressure
Hoses are at most 15 m long in machinery spaces and 20 m on open decks (SOLAS II-2/10.2.3.1.1). Hydrant pressure must stay low enough for the hose team to hold the branch (10.2.1.6.3); UK surveyors want to see that demonstrated above 7 bar. The amber band on the hydrant gauge starts there.
Check yourself
Why does the fire main have an isolating valve just outside the engine room?
- To keep the main under pressure when pump No.1 stops, so the next start is quicker
- To stop water running back through pump No.1 when the emergency fire pump runs
- To cut off the engine room section, so the emergency fire pump can still supply every other hydrant — correct
A fire or a burst pipe in the engine room can take out pump No.1 and its part of the main. With the isolating valve shut, the emergency fire pump in the bow thruster room still feeds every hydrant outside the engine room (SOLAS II-2/10.2.1.4.1). Back-flow through pump No.1 is stopped by its screw-down non-return valve, not by this valve.
Sources
- SOLAS II-2/10, fire fighting: fire pumps, fire main, hydrants (consolidated text, imorules.com)
- FSS Code ch. 12, emergency fire pumps: IMO res. MSC.98(73), as adopted
- IMO MSC.1/Circ.1314, emergency fire pump capacity and hydrant pressure (German flag copy)
- UK MCA MSIS 12 ch. 5: fire pumps, fire mains, hydrants and hoses (non-return valves, hose control above 7 bar)
For training only. Models are simplified; class rules and IMO texts are the authority.