Lock-out / tag-out in the engine room

CHIEF. LEARN · Guide 7 of 7

Isolating machinery before work on board: the permit to work, every energy source, the breaker locked off, your own lock and DANGER tag, the test for dead, and who removes the lock.

The example throughout is the engine control room of a Supramax bulk carrier: three diesel generators on a 440 V, 60 Hz main switchboard with a bus-tie and a power management system, an emergency generator feeding the emergency switchboard, the main engine controlled from the ECR console, and a UV ballast water treatment system.

MSB
main switchboard
MCCB
moulded-case circuit breaker
AMS
alarm and monitoring system
ECR
engine control room
ACB
air circuit breaker: the generator breaker on the main switchboard
PMS
power management system: starts, connects and shares the generators
LOTO
lock-out / tag-out
OOW
officer of the watch
MCC
motor control centre
CPR
cardiopulmonary resuscitation
AED
automated external defibrillator

Why a lock and not just a switch

Isolation accidents on board tend to start the same way: someone switches off a pump or a fan, someone else does not know, and it starts again. From the ECR, through the PMS or the AMS, from a local panel, or by itself as the standby machine.

LOTO makes the isolation physical and personal. The energy is cut at its source, the breaker is locked in OFF with a lock only you can open, and a tag says who is working on it and since when.

In the ECR trainer the procedure hangs on the bulkhead as a poster. The steps below follow it.

Step by step

  1. Inform the OOW and the chief engineer, and get the permit to work your safety management system asks for.
  2. Identify all the energy sources: electric, hydraulic, pneumatic and stored.
  3. Switch off at the MSB or at the MCC starter.
  4. Rack out the ACB, or lock the MCCB in OFF.
  5. Fit your personal lock and a DANGER tag: DO NOT OPERATE, with your name and the date.
  6. Test for dead: try a local start, and check with a proven voltage detector.
  7. Do the work.
  8. Remove only your own lock, and only when everyone is clear.

Every energy source, not only the cable

Switching off the motor does not empty a pipe under pressure, an accumulator, an air receiver or a spring. Close and lock the valves, vent and drain what the job opens, and let hot parts cool.

A motor’s anti-condensation heater is often fed from a separate circuit and stays live after the main breaker is off. So can a control circuit fed from another panel.

A standby pump with its starter in AUTO starts by itself when the pressure falls. Take it out of AUTO and isolate it too, or your job on one pump starts the other.

One person, one lock

Everyone who works on the equipment fits their own lock. With several people, a hasp or a lock box takes them all, and the equipment cannot be switched on until the last lock is off.

Never remove someone else’s lock. If its owner has gone ashore or left the ship, your company’s procedure decides, usually through the chief engineer, after the equipment has been checked.

At a change of watch the job keeps its isolation: the person coming on fits their lock before the person going off removes theirs.

Test for dead

A lock proves that the breaker you locked is off. It does not prove that the equipment in front of you is dead: the wrong breaker, a back-feed or a second supply all look the same from the switchboard.

Try a local start with the isolation in place: nothing must move. Then check with a voltage detector proven on a known live source before and after the test: live, dead, live.

If someone gets a shock

  1. Do not touch the casualty.
  2. Switch off at the MSB feeder breaker or the local isolator.
  3. If you cannot switch off, separate the casualty from the supply with a dry insulating object.
  4. Raise the alarm and call the bridge.
  5. Check response and breathing.
  6. Not breathing: start CPR, 30 compressions and 2 breaths.
  7. Use an AED, if the ship carries one, as soon as it arrives.
  8. Cool burns with water and keep the casualty warm.
  9. Get radio medical advice.

Try it in the simulator. Parallel a generator, bring the plant back after a blackout and start the main engine in a walk-in 3D engine control room, with a score for each scenario. Free, in your browser on a computer, with a free CHIEF. account.

Open ECR — Engine Control Room →

Check yourself

Two people work on the same pump. How many locks go on its isolator?
  1. Two: one each — correct
  2. One, from the senior person
  3. None, if the DANGER tag is on

One person, one lock. The pump cannot be switched on until both have finished and removed their own locks.

The breaker is locked off. What do you do before you touch the terminals?
  1. Test for dead: a local start, then a proven voltage detector — correct
  2. Start work: the lock is enough
  3. Ask the bridge to confirm

The lock proves the breaker is off, not that the equipment is dead. A wrong breaker or a second supply only shows up in the test.

A colleague has gone ashore and left their lock on. Can you remove it?
  1. Not on your own: the company procedure decides, through the chief engineer — correct
  2. Yes, if the job looks finished
  3. Yes, if the work is urgent

A lock is removed by the person who fitted it. Anything else follows the company’s procedure, after the equipment has been checked.

Sources

  • UK MCA Code of Safe Working Practices for Merchant Seafarers: permit to work, isolation (gov.uk copy)
  • HSE HSG85: Electricity at work, safe working practices
  • HSE GS38: electrical test equipment for use on low voltage electrical systems

For training only. The room, the switchboard and the sequences are simplified; class rules, the makers’ manuals and your company’s procedures are the authority.

← PreviousBallasting through the ballast water treatment systemAll guides →ECR — Engine Control Room guides
Built by CHIEF.

Free for seafarers: CV, certificates, sea service

These trainers are made by CHIEF., the career platform for seafarers. Keep your STCW certificates with expiry reminders, log sea service and send a ready CV to crewing companies.

Free to startiPhone, Android, any browserOne account
Create a free accountiOS app on the App Store →Android app on Google Play →

Already have an account? The button opens it.

CHIEF.
LearnCertificate trackerCV builderSeafarer CVSTCW certificatesSea-time calculatorCountry guidesWeb appiOS appAndroid appContact
© 2026 CHIEF. · Maritime Reconnected
support@chief.directPrivacyTermsUAru