Blackout on a ship: restoring main power from the ECR
CHIEF. LEARN · Guide 2 of 7
What to do in the engine control room when the main switchboard goes dead: the emergency generator, the cause, the standby generator on the dead bus, the essential consumers and the bridge.
The example throughout is the engine control room of a Supramax bulk carrier: three diesel generators on a 440 V, 60 Hz main switchboard with a bus-tie and a power management system, an emergency generator feeding the emergency switchboard, the main engine controlled from the ECR console, and a UV ballast water treatment system.
- MSB
- main switchboard
- AMS
- alarm and monitoring system
- ECR
- engine control room
- DG
- diesel generator
- ACB
- air circuit breaker: the generator breaker on the main switchboard
- PMS
- power management system: starts, connects and shares the generators
- EDG
- emergency diesel generator
- ESB
- emergency switchboard
What happens in a blackout
The generator on the bus trips. In the trainer DG1 shuts down on low lubricating oil pressure. The main bus goes dead, every pump and fan on it stops, and the main engine loses its pumps and stops with them. The ship is not under command.
The emergency switchboard (ESB) is fed from the MSB through an interconnector. On a blackout the interconnector opens, a battery keeps the transitional lighting on, and the emergency generator (EDG) starts by itself. SOLAS gives it 45 seconds to be on load, feeding the emergency lighting, the steering gear, the emergency fire pump, the radio and the navigation lights.
On many ships the PMS starts the standby generator and closes it onto the dead bus by itself within seconds. The steps below are what you do when it does not, or when the PMS is in manual. They follow the blackout recovery poster on the ECR bulkhead in the trainer.
Immediate actions
- Inform the bridge: main engine stopped, the ship may not be under command.
- Check the EDG is on load: the ESB is live, the emergency lighting is on and the steering gear is available.
- Find the cause: the AMS alarm list, the trip flags on the ACBs and the PMS event log. Acknowledge the alarms on the AMS.
Restoring main power
- Reset a tripped ACB only after its fault has been found and cleared. In the trainer DG1 has an engine shutdown: leave it.
- Start the standby DG, DG2 or DG3, and check 440 V and 60 Hz on its panel.
- Close its ACB onto the dead bus. A dead bus needs no synchronising: there is nothing to be in step with.
- Restart the essential consumers in sequence: steering gear, lubricating oil pumps, cooling water, fuel supply. In the trainer they are started from group starter panels GSP1 and GSP2.
- Parallel a second DG, synchronising it as usual, and share the load before the main engine is restarted.
After main power is back
About five seconds after the main bus is live, the ESB transfers back to the MSB by itself: the EDG panel shows ESB FED BY MSB. The EDG runs on to cool down and stops; check that its mode switch is back in AUTO.
Report to the chief engineer and record the blackout, its cause and the times in the engine log book. Inform the bridge when the main engine is ready again.
When the emergency generator does not start
In the trainer’s second blackout the previous watch left the EDG mode switch in MAN. The main bus dies, nothing starts, and the emergency switchboard stays dead too: no emergency lighting, no steering gear.
Start the EDG by hand at the EDG / ESB remote panel with EDG START, then turn the mode switch back to AUTO. Acknowledge the alarms, put a standby generator on the dead bus and let the ESB transfer back to the MSB.
The lesson is the handover: check the EDG mode when you take the watch, and after every test. The poster’s NEVER list says it plainly: never close a breaker onto a fault, never parallel without synchronising, never leave the EDG in MAN or OFF.
Check yourself
You put the standby generator onto a dead main bus. Do you need to synchronise?
- No: a dead bus has nothing to be in step with — correct
- Yes, always
- Only if the EDG is running
Synchronising matches a machine to a live bus. On a dead bus the first generator simply closes on; the second one is synchronised as usual.
A generator ACB has tripped. When may you reset it?
- After the fault is found and cleared — correct
- At once, to restore power faster
- After the EDG is on load
Closing a breaker onto a fault can repeat the trip or cause damage. Find and clear the cause first.
After a blackout the emergency switchboard is dead too. What is the first thing to check?
- The EDG mode switch: it may be in MAN or OFF — correct
- The bus-tie breaker
- The synchroscope
An EDG in AUTO starts by itself. If the ESB stays dead, start it by hand and put the mode back to AUTO.
Sources
For training only. The room, the switchboard and the sequences are simplified; class rules, the makers’ manuals and your company’s procedures are the authority.