Engine room fire: first actions from the ECR
CHIEF. LEARN · Guide 4 of 7
A fire alarm in the purifier room: silence and acknowledge, inform the bridge, call the engineers, stop the purifiers and the fans, and why fixed CO₂ is the Master’s order.
The example throughout is the engine control room of a Supramax bulk carrier: three diesel generators on a 440 V, 60 Hz main switchboard with a bus-tie and a power management system, an emergency generator feeding the emergency switchboard, the main engine controlled from the ECR console, and a UV ballast water treatment system.
- ECR
- engine control room
- FO
- fuel oil
The alarm
In the trainer the fire detection system raises zone 12: engine room, purifier room. The red fire alarm repeater panel on the ECR bulkhead shows the zone and sounds its buzzer.
Silencing the buzzer and acknowledging the alarm do not deal with the fire. They tell the system someone has seen it. The zone stays in alarm until the fire is out and the alarm is reset.
Step by step
- On the fire alarm repeater panel: SILENCE BUZZER, then ACKNOWLEDGE.
- Inform the bridge on the sound-powered telephone: selector 1, BRIDGE, lift the handset.
- Sound the engineers’ alarm with the red ENGINEERS’ ALARM button in the COMM section. It is operated from the ECR and heard in the engineers’ accommodation.
- Stop the purifiers from the group starter panels GSP1 and GSP2: FO purifier 1, FO purifier 2 and the LO purifier. They are in the space on fire and they feed it oil.
- Stop the engine room supply fans from GSP1 and GSP2. Do not feed the fire with air.
- When the fire party reports the fire is out and the space has been checked, reset the fire alarm on the repeater panel.
The action plan on the ECR bulkhead
The trainer’s engine room fire poster puts the same work in three groups.
Raise the alarm: a fire alarm call point, the bridge informed, the fire party mustered and everyone in the engine room accounted for.
Contain: stop the ventilation fans and close the fire dampers and skylights; use the remote stops for the fuel oil and lubricating oil pumps, the purifiers and the ventilation; close the quick-closing valves on the fuel oil and lubricating oil tanks; cool the boundaries and check the spaces next to the fire.
Fight: portable extinguishers only on a small fire, with a clear escape behind you; otherwise the fire party in breathing apparatus, with the hose under pressure.
The remote stops and the quick-closing valves are worked from outside the space so that you do not have to go in. They only help if they work: test them as your planned maintenance says.
Fixed CO₂: only on the Master’s order
The fixed CO₂ system floods the engine room with enough gas to put out the fire, and enough to kill anyone still inside. It is released only on the Master’s order, after a head count, with the engine room evacuated and sealed.
Sealed means every opening closed and every fan stopped. Air that gets back in feeds the fire again and lets the gas out.
Check yourself
You have acknowledged the fire alarm. What has that done about the fire?
- Nothing: it only tells the system the alarm was seen — correct
- It has started the fixed CO₂ system
- It has stopped the fans
Acknowledge is not action. Inform the bridge, call the engineers and stop the fuel and air to the space.
Why stop the engine room supply fans?
- They feed the fire with air — correct
- To save power
- To hear the alarm better
Fuel and air keep a fire going. Stopping fans and closing dampers and skylights starves it, and is needed before any fixed system is used.
Who decides to release the fixed CO₂ system?
- The Master, after a head count and with the space sealed — correct
- The engineer on watch
- The first person who sees the fire
CO₂ kills. It is released only on the Master’s order, with everyone out and the engine room sealed.
Sources
- IMO res. A.1021(26), Code on Alerts and Indicators: the engineers’ alarm
- IMO MSC.1/Circ.1434, unified interpretations of SOLAS chapter II-2 (German flag copy)
- AMSA Marine Notice 2024/05: fuel isolation for multi-engine installations (remote quick-closing valves)
For training only. The room, the switchboard and the sequences are simplified; class rules, the makers’ manuals and your company’s procedures are the authority.