Oil mist detector: the weekly function test

CHIEF. LEARN · Guide 5 of 7

Why a main engine has a crankcase oil mist detector, what the weekly test proves, and the sequence from the ECR: bridge, TEST, alarm and slowdown, acknowledge, reset.

The example throughout is the engine control room of a Supramax bulk carrier: three diesel generators on a 440 V, 60 Hz main switchboard with a bus-tie and a power management system, an emergency generator feeding the emergency switchboard, the main engine controlled from the ECR console, and a UV ballast water treatment system.

AMS
alarm and monitoring system
ECR
engine control room
OMD
oil mist detector

Why the main engine has one

A hot spot in the crankcase, such as a running bearing or a piston blowing by, heats the lubricating oil until it boils off and condenses into a fine mist. Mixed with air in the crankcase, that mist can ignite and explode. Crankcase explosions have killed engine crews; the relief valves on the crankcase doors are there for that reason.

An OMD draws samples from each crank space and measures the mist. When one rises above its alarm level, it raises the alarm before the mist can reach an explosive concentration.

Under SOLAS, engines of 2,250 kW and above, or with cylinders of more than 300 mm bore, have crankcase oil mist detectors, engine bearing temperature monitors or equivalent devices. On a slow-speed main engine the detector raises the alarm and requests a slowdown; on medium and high-speed engines it is part of the automatic shutdown (IMO MSC.1/Circ.1345).

What the weekly test proves

The test simulates mist on one cylinder and follows it through: the detector sees it, the alarm reaches the AMS, and the slowdown request reaches the main engine safety system.

Because the slowdown request is real, the bridge must know before you press TEST. On a ship under way an unannounced slowdown is a surprise nobody needs.

Step by step

  1. Inform the bridge: OMD test, a slowdown request is possible. Sound-powered telephone, selector 1, BRIDGE.
  2. Press TEST on the black OIL MIST DETECTOR panel on the ECR bulkhead. In the trainer the test runs on cylinder 4.
  3. Confirm the result: the reading of cylinder 4 rises above the alarm line, and the ALARM and SLOWDOWN lamps light.
  4. Acknowledge the alarm on the AMS.
  5. Wait until the reading falls back below the limit, 0.70 mg/l in the trainer, then press RESET on the OMD panel. A reset is refused while the level is still high.

If it is not a test

A real oil mist alarm is treated as a hot spot until proven otherwise: the engine is slowed down or stopped as the maker and your company require, and nobody stands near the crankcase relief valves.

Crankcase doors are not opened until the engine has stopped and cooled for the time the maker gives. Fresh air into a hot crankcase full of mist is how a second explosion happens.

Try it in the simulator. Parallel a generator, bring the plant back after a blackout and start the main engine in a walk-in 3D engine control room, with a score for each scenario. Free, in your browser on a computer, with a free CHIEF. account.

Open ECR — Engine Control Room →

Check yourself

Why inform the bridge before the weekly OMD test?
  1. The test sends a real slowdown request to the main engine — correct
  2. The bridge must press TEST
  3. The test stops the generators

The test runs through to the engine safety system. The bridge must not be surprised by a slowdown.

You press RESET and the OMD refuses it. Why?
  1. The mist level is still above the limit — correct
  2. The bridge has not answered
  3. The AMS is not acknowledged

The detector resets only once the reading has fallen below the alarm level.

Sources

  • IMO MSC.1/Circ.1345, interpretation of SOLAS II-1/27.5: crankcase oil mist detectors (Traficom copy)
  • IACS Unified Requirements: UR M3 (governors, load sharing of generators in parallel) and UR M10 (crankcase protection)

For training only. The room, the switchboard and the sequences are simplified; class rules, the makers’ manuals and your company’s procedures are the authority.

← PreviousEngine room fire: first actions from the ECRNext →Ballasting through the ballast water treatment system
Built by CHIEF.

Free for seafarers: CV, certificates, sea service

These trainers are made by CHIEF., the career platform for seafarers. Keep your STCW certificates with expiry reminders, log sea service and send a ready CV to crewing companies.

Free to startiPhone, Android, any browserOne account
Create a free accountiOS app on the App Store →Android app on Google Play →

Already have an account? The button opens it.

CHIEF.
LearnCertificate trackerCV builderSeafarer CVSTCW certificatesSea-time calculatorCountry guidesWeb appiOS appAndroid appContact
© 2026 CHIEF. · Maritime Reconnected
support@chief.directPrivacyTermsUAru