AUTO and lead / lag: two compressors on the receivers

CHIEF. LEARN · Guide 3 of 5

Two main air compressors on the receivers: pressure switches at 27/30 and 24/30 bar, lead and lag, the STOP button trap in AUTO and the restart after a blackout.

The example throughout is No.1 main air compressor of a ship: a 30 kW motor on a 440 V, 60 Hz supply with a relay starter panel (SP-MAC1) and 220 V control voltage, charging two 3 m³ receivers to 30 bar.

AMS
alarm and monitoring system
HMI
human–machine interface: the display on the panel door

AUTO and lead / lag

AUTO between 27 and 30 bar

Mechanics
Nothing starts: the receivers are above the start setting of the lead switch.
Electrics
S1 AUTO puts wire 7 on wire 9. S2 LEAD passes it to wire 10 → X1:6 → PS1. PS1 is open: it last opened at 30 bar and closes again only below 27.
What you see and hear
No change.

Pressure falls below 27 bar

Mechanics
The compressor starts and loads after 15 s, as in MAN.
Electrics
PS1 closes: wire 12 → KA1 coil. KA1 11-14 puts wire 9 on wire 14 → KM1. KA1 21-24 energises K12: AUTO DEMAND to the AMS.
What you see and hear
RUNNING lit; the AMS sees DEMAND and RUNNING.

30 bar: stop

Mechanics
Stopped by pressure; the drains open and unload the stages.
Electrics
PS1 opens at 30 bar: KA1 drops, KM1 drops.
What you see and hear
Drains blow briefly, RUNNING off.

The STOP button trap

Mechanics
It stopped while STOP was held and started again when it was released.
Electrics
STOP S4 sits before S1, so it also cuts KA1. On release PS1 is still closed: KA1 and KM1 pull in again. To stop a compressor in AUTO, turn S1 to OFF.
What you see and hear
RUNNING off for a moment, then on again. In this design, a classic watchkeeping surprise.

Lead or lag

Mechanics
As lag, No.1 waits for 24 bar: it only helps when the lead compressor cannot keep up.
Electrics
S2 LAG moves wire 9 to wire 11 → X1:8 → PS2 (start 24 bar, stop 30 bar) → X1:9 → wire 12. No.2 has the opposite S2 position.
What you see and hear
At 26 bar nothing starts.

After a blackout

Mechanics
When power comes back, a compressor in AUTO with pressure below the setting starts by itself, after the delay of the ship's sequential restart.
Electrics
Nothing latches the stop: when 220 V returns, PS1 is still closed and KA1, KM1 pull in. Limit: no more than 6 starts an hour for the motor; a leak in the air line shows up as more starts per hour on the HMI.
What you see and hear
Back to RUNNING after the supply returns.

Try it in the simulator. Find eleven faults on the compressor starter with the drawings, a multimeter and a clamp meter, in a 3D compressor room. Free, in your browser, no account.

Open ETO Fault Finding →

For training only. Models are simplified; class rules and the maker’s manual are the authority.

← PreviousStarting a main air compressor: checks, first run, start sequenceNext →Stopping, trips and AMS alarms
Built by CHIEF.

Free for seafarers: CV, certificates, sea service

These trainers are made by CHIEF., the career platform for seafarers. Keep your STCW certificates with expiry reminders, log sea service and send a ready CV to crewing companies.

Free to startiPhone and any browserOne account
Create a free accountiOS app on the App Store →

Already have an account? The button opens it.

CHIEF.
LearnCertificate trackerCV builderSeafarer CVSTCW certificatesSea-time calculatorWeb appiOS appContact
© 2026 CHIEF. · Maritime Reconnected
support@chief.directPrivacyTermsUAru