Starting a main air compressor: checks, first run, start sequence

CHIEF. LEARN · Guide 2 of 5

Checks before starting a ship’s main air compressor, the first run after overhaul and the start in MAN step by step: contactor, timers, oil pressure and loading.

The example throughout is No.1 main air compressor of a ship: a 30 kW motor on a 440 V, 60 Hz supply with a relay starter panel (SP-MAC1) and 220 V control voltage, charging two 3 m³ receivers to 30 bar.

NC / NO
normally closed / normally open contact
ETO
electro-technical officer
AMS
alarm and monitoring system
HMI
human–machine interface: the display on the panel door
LP / HP
low pressure / high pressure (first / second stage)

Preparing to start

Mechanical checks

Mechanics
Oil level on the dipstick, no water in the oil. Cooling water valves open and flow visible in the sight glass. Discharge valve V3 open: a start against a closed V3 drives HP up to SV2. Manual drains V1, V2 open. Turn it over by hand, nobody near the machine.
Electrics
Nothing switched yet. After work on the motor or its cable the ETO checks insulation with a 500 V megger: more than 1 MΩ is acceptable, a healthy motor shows well over 100 MΩ.
What you see and hear
At the compressor: valve handles, the sight glass, the oil gauge at zero.

Power on

Mechanics
Still standing.
Electrics
Lock removed, Q1 on: T1 gives 220 V on wire 1 (X1:1) and wire 2 (X1:2). POWER ON lights. The motor heater HM1 is on through KM1 21-22.
What you see and hear
POWER ON lit, HMI STOPPED, ammeter at zero.

First run

Mechanics
A short start checks the direction of rotation after work on the motor or cable. Then start in MAN, close V1 and V2 after a few minutes, check stage pressures, oil and water. After 30 minutes stop, feel the bearings, then put it in AUTO.
Electrics
The MAN start is shown step by step below. In MAN the protections still work: the oil and temperature trips and the overload are not bypassed.
What you see and hear
With V1 and V2 open the compressor cannot load: air blows from both drains.

Start in MAN

Standing, ready

Mechanics
Stopped. Both stages at zero, YV1 and YV2 open.
Electrics
220 V on X1:1. The protection chain is closed: wire 3 (after S0) → F4 95-96 → wire 4 → KA2 11-12 → wire 5 → KA3 11-12 → wire 6. KM1 21-22 feeds the motor heater on wire 32.
What you see and hear
POWER ON lit, HMI STOPPED.

S1 to MAN

Mechanics
Nothing moves yet.
Electrics
Through STOP S4 (NC) wire 7 is live, and S1 MAN puts it on wire 8. Wire 8 waits at START S3 and at KM1 13-14, both open.
What you see and hear
No change on the door.

START pressed

Mechanics
The motor starts direct on line, unloaded.
Electrics
S3 puts wire 8 on wire 14: KM1 coil pulls in. KM1 13-14 closes in parallel with S3 (self-hold), 43-44 starts KT1 on wire 20, 53-54 makes wire 26 live: RUNNING H2, K10 to the AMS, the running-hours meter, KT3, and through F5 the water solenoid YV3. KM1 21-22 opens: motor heater off.
What you see and hear
Contactor click, RUNNING lit, the ammeter kicks to full scale.

START released: self-hold

Mechanics
The motor runs up in about a second. Both drains whistle: the compressor turns but does not pump.
Electrics
KM1 holds itself through 13-14. The starting current, about 310 A on the 8 % voltage dip, falls to about 17 A once the motor is up to speed.
What you see and hear
Whistling drains, the ammeter drops to 17 A.

Oil pressure builds

Mechanics
The gear pump on the crankshaft only delivers once the shaft turns: oil pressure rises to 2.2 bar within a few seconds.
Electrics
PS3 opens above 1.2 bar. It is not in the trip circuit yet: KT1 keeps the oil trip bypassed for 20 s.
What you see and hear
Oil gauge to 2.2 bar.

15 s: loading

Mechanics
YV1 and YV2 close; the compressor starts pumping. LP rises to 4–5 bar, HP to the receiver pressure.
Electrics
KT3 15-18 closes after 15 s: wire 27 → wire 28 → KT2 15-16 (closed) → wire 29 → YV1 (X1:16) and YV2 (X1:18) get 220 V.
What you see and hear
The whistle stops, the sound of the machine changes, the current rises.

20 s: oil trip armed

Mechanics
Pumping.
Electrics
KT1 15-18 closes: from now on PS3 closing (oil below 0.8 bar) energises KA2 through wire 21 → X1:10 → PS3 → X1:11 → wire 22, and the compressor trips.
What you see and hear
Nothing visible: the bypass ends quietly.

Pumping in MAN

Mechanics
It pumps the receivers up about 0.3 bar a minute against normal consumption.
Electrics
Current 46–48 A at 27–30 bar. In MAN it does not stop on pressure: only STOP or S1 to OFF stops it. The protections still act in MAN.
What you see and hear
Ammeter about 47 A, HMI LOADED.

Try it in the simulator. Find eleven faults on the compressor starter with the drawings, a multimeter and a clamp meter, in a 3D compressor room. Free, in your browser, no account.

Open ETO Fault Finding →

For training only. Models are simplified; class rules and the maker’s manual are the authority.

← PreviousHow a ship’s main air compressor worksNext →AUTO and lead / lag: two compressors on the receivers
Built by CHIEF.

Free for seafarers: CV, certificates, sea service

These trainers are made by CHIEF., the career platform for seafarers. Keep your STCW certificates with expiry reminders, log sea service and send a ready CV to crewing companies.

Free to startiPhone and any browserOne account
Create a free accountiOS app on the App Store →

Already have an account? The button opens it.

CHIEF.
LearnCertificate trackerCV builderSeafarer CVSTCW certificatesSea-time calculatorWeb appiOS appContact
© 2026 CHIEF. · Maritime Reconnected
support@chief.directPrivacyTermsUAru